How it works
The parts of a backflow preventer, shown on a reduced pressure zone assembly: two check valves in a row with a relief valve between them. The first drawing is the assembly in a water line; the second is its body cut open.
Read the full guide
Outside: follow the water
Water comes in from the left. It passes the strainer and the No. 1 shutoff valve, runs through the body and leaves by the No. 2 shutoff valve. The four test cocks are numbered the same way, 1 to 4. The relief valve hangs under the body, over the air gap and the drain.
Inside: two checks and a zone
Each check valve is pressed onto its seat by a spring under a cover. Water has to push the first one open, then the second. The space between them is the reduced pressure zone. If the pressure there climbs too close to the supply pressure, the relief valve opens and lets water out.
- A double check valve assembly has the two check valves, the test cocks and the shutoff valves, but no relief valve.
- The numbers run with the flow: No. 1 is always at the inlet end.
Questions and answers
What are the parts of a backflow preventer?
A reduced pressure zone assembly has two shutoff valves, four test cocks, two spring-loaded check valves, the zone between them and a relief valve that opens to the air. A strainer ahead of it and an air gap under it complete the installation.
What does the relief valve on a backflow preventer do?
It keeps the zone between the two check valves at a lower pressure than the supply. If that pressure rises, because a check valve leaks or water pushes back, the relief valve opens and the water falls out through the air gap.
What are the test cocks on a backflow preventer for?
They are small valves where a certified tester connects the hoses of a differential pressure gauge. The readings show whether each check valve holds and whether the relief valve opens when it should, without taking the assembly apart.
What is the difference between an RPZ and a double check valve?
Both have two check valves in a row. A reduced pressure zone assembly adds a relief valve between them, which lets water out if a check valve leaks. A double check valve assembly has none and is not used where the hazard is high.